In toilets: the ALIZÉ TEMPO (TW) grille provides a permanent flow of 5 m³/h and an additional timed flow of 30 m³/h.
The vent can be mounted on a wall or ceiling, in compliance with the following requirements:
In the wall position, the vents are mounted by a simple interlocking system on a Ø 125 mm duct or on a Ø125 mm sleeve to be sealed. The lip seal provides retention and sealing.
On the ceiling, the implementation can be carried out using a drywall 3-claw adapter sleeve or a Ø125 mm through-slab sleeve.
The vents have 3 fixing holes. It is advisable to screw the vents to the wall or ceiling using the 3 holes provided for this purpose. The electric vents must be fixed.
The vents have a cable grommet for the power supply and for the push button. See diagram opposite.
• Cord control: When mounting on a ceiling, it is necessary to use an angle piece to guide the cord.
• 230 V power supply: the vent must be powered by a 2-wire cable (2 x 1.5 mm²) that must be built in and must come out at the back of the support plate. This power supply must include a suitable protection device identified on the electrical panel in order to be able to carry out interventions on the vent.
Class II electrical appliance.
It is advisable to screw the grille support plate to the wall or the ceiling using the 3 holes provided on the plate.