The ALIZE CO2 extract used for tertiary applications ensure a modulated extraction flow from 10 to 100m3 /h under 80 Pa according to the CO2 rate of the room in which they are installed.
Principle :
The ALIZÉ C02 adapts its flow rate in stages (10, 25, 50, 75 or 100% opening) according to 3 triggering thresholds.
With the help of the VMC Connect application for smartphone (iOS or Android), it is possible to control and monitor the extract vent and to read the hygrometry and the CO2 rate of the room in which they are installed. A flow reading is also available.
Mounting can be done in a wall or ceiling position, in compliance with the following requirements:
In the wall position, the vents are mounted by a simple interlocking system on a Ø 100 mm duct or on a Ø125 mm sleeve to be sealed. The lip seal provides support and sealing.
On the ceiling, the implementation can be carried out using a drywall 3-claw adapter Ø100 or Ø125.
Two-wires cable (2 x 1.5 mm²) supply power to the valve, leading to the back of the support plate (see diagram).
After taking off the grill , remove the electrical terminal box. Route the wires through the opening at the back of the support plate.
– 230 V power supply : remove the violet front case of the electrical terminal box, connect the electrical wires on it and put back the cover.
– 12 V power supply : connect directly the wires to the electrical box.